Products and Prices

Please choose any category to view our latest prices. Please note that prices exclude VAT at the current rate, may change without notice and prices shown on this page should be used as a guide.

Wireless Detect

SRC 3000 – the Wire-Free alternative to Conventional Fire Panels from Detectomat

A unique Wire-Free, Radio Fire System offering an alternative to the costs, potential damage and business disruption associated with installing Fire systems in existing buildings. And an ideal solution for retrofit and refurbishment applications in small to medium sized enterprises (buildings, office buildings, guest houses, restaurants,nursery schools, garages / workshops, large houses and houses in multiple occupation).

Features:
A wide range of radio devices including detectomat’s designer range of smoke detector/alarms, heat detector/alarms and manual call points plus:

  • Fast reset and control functions
  • Integral radio strength check/measurement for operational devices
  • Integral service/inspection mode
  • Temporary alarm silence function
  • External, remote, radio reset function via module
  • 4 integrated programmable control relays, normally energised or de-energised with changeover contacts
  • Standard panel available in English or German, additional languages possible
  • User-friendly application via LCD display
  • Radio controlled panel utilising unique encoding in the ISM band (433 MHz) to connect up to 100 radio detection devices
  • Extension of the 100M LOS operating distance via radio wireless repeaters
  • Bi-directional radio control and alarm functions
  • 6 alarm zones with individual identification of the device in alarm
  • Control / monitoring and testing functions for all radio devices (fault, error, change of battery, radio integrity)
  • Integrated power supply for 230 V connection
  • Internal battery back-up
  • Addressable Loop 3000 connection via IOM 3311
  • No Wires
  • No Mess
  • No Disruption
  • Just Quick & Stylish

Radio / Wireless Control Panel SRC 3000
The microprocessor-controlled SRC 3000 radio fire control panel with life cycle monitoring is designed for connection of up to 100 radio devices
- 6 alarm zones
- acoustic and optical signalling of alarm and fault conditions
- individual identification and monitoring of the radio devices relating to individual battery condition, detector condition and radio integrity

Wireless Fire System
system voltage 230 V AC / 50 Hz or external 12v DC supply
frequency 433 MHz
operation voltage 12 V DC
emergency power supply 8 x 1.5 V type Mignon, LR 6
nominal current ca. 35mA (LED operation), max. 120mA (4 relays in break circuit mode)
alarm current max. 160 mA (in reference of the operation mode)
display LCD
alarm and status indicators LED
outputs 4 x relay changeover contact via additional cable F.BZ (32294) SUB-D plug-type connector
switching voltage / - current 30 V AC / 1 A
acoustic signalling 85dB (1 m)
radio transmission power 10 mW ERP
operating temperature 0° ti +60°C
dimensions (H x W x D) 170 x 170 x 55 mm
place of installation suitable for dry, heated rooms
weight 800g
RoHS conform yes

Wireless sounder / beacon FABM SRC 3000
for direct interface connection via radio control panel SRC 3000

Wireless Fire System
frequency433 MHz
power supply2 x 3V
normal operation current45 µA
transmission current350 mA
operating temperature0°C to 55°C
dimensions121 x 93mm

Radio repeater FRP SRC 3000
to extend the transmission path of the bi-directional system devices and the radio control panel SRC 3000
- 10 radio devices / repeater
- 3 repeaters / SRC 3000 signal strength display
- transmission of detector signal
- function monitoring
- wall mounting

Wireless Fire System
power supply230 V AC / 12 V DC via seperate mains transformer
frequency433MHz
battery backup9 V
quiescent current35 mµ
normal operation current35 mA
transmission current90 mA
operating temperature0°C to 60°C
dimensions (H x W x D)158 x 95 x 45mm

Optical Smoke Detector / Alarm HDv 3000 0
Battery powered optical smoke detector / alarm certified to EN 114604. Also available in different designs.

Wireless Smoke Detector
acoustic alert 85 dB
power supply 9V
responsivity < 0, 15 dB/m
operating temperature -10°C to 60°C
VdS certification no. G202 042
DIN-EN 14604
dimensions 51 including base x 100mm

Radio Module FM SRC 3000
plug-in radio module for the smoke detector / alarm HDv 3000 O to report and receive alarm and fault conditions via radio control panel SRC 3000.

Wireless Fire System
frequency433 MHz
power supply9 V
normal operation current50 µA
transmission current40 mA
operating temperature0°C to 55°C

Heat Detector / alarm HD 3000 T
battery powered heat detector alarm.

Wireless Fire System
acoustic alert85dB
power supply9 V
operating temperature0°C to 65°C
responsivity60°C
dimensions70 x 80 mm

Radio Module FM SRC 3000
plug-in radio module for the heat detector / alarm TM to report and receive alarm and fault conditions via radio control panel SRC 3000.

Wireless Fire System
frequency433 MHz
power supply9 V
normal operation current50 µA
transmission current40 mA
operating temperature0°C to 55°C

Radio manual call point FMCP SRC 3000
for the manual release / activation of a fire alarm interlinked to the radio fire control panel SRC 3000.

Wireless Fire System
frequency433 MHz
power supply9 V
normal operation current15 µA
transmission current25 mA
operating temperature0°C to 55°C
dimensions (H x W x D)93 x 89 x 59mm

Radio input module FIB SRC 3000
general purpose radio input module for the SRC 3000

Wireless Fire System
frequency433 MHz
power supply9 V
normal operation current35 µA
transmission current25 mA
operating temperature0°C to 55°C
dimensions (H x W x D)93 x 57 x 30mm

Radio reset module FIB SRC 3000
The integrated radio module sends a reset signal to the SRC 3000 panel

Wireless Fire System
frequency433 MHz
power supply9 V
normal operation current35 µA
transmission current25 mA
operating temperature0°C to 55°C
dimensions (H x W x D)93 x 57 x 30mm

No products found.

« Back

Fire Extinguishers and Equipment Access Control Systems CCTV Credit Cards